Wire gauge·AWG 14 · 3A
AWG 14general outlets
139.1m
3A · Europe 230 V

AWG 14 carrying 3 A — 0.5 V over 10 m

2.081 mm² of copper, 0.00827 Ω per metre. Carrying 3 A, a ten-metre run there and back loses 0.5 V.

This gauge handles it · Current it handles 14.8A

Diameter
1.628 mm
Cross-section
2.081 mm²
Resistance per metre
0.00827 Ω
Current it handles
14.8 A
Drop over 10 m
0.5 V
Heat per metre
0.07 W

Length within 3%

Lose the same 0.36 V and it is 3% of a 12 V system but 0.16% of a 230 V one. That is why car wiring looks so thick, and why a long 12 V light run dims at the far end. This page works out the length that stays under 3% for each voltage separately.

  • car 12 V7.3 m
  • truck 24 V14.5 m
  • North America 120 V72.6 m
  • Europe 230 V139.1 m

The match in the other family

The United States names wire by AWG number; most of the world names it by cross-section in mm². The two never line up exactly, so each page shows the nearest match by area. When substituting, err toward the thicker one.

2.5mm²2.5mm²

Nearby cells

Same gauge, other currents

Same current, other gauges

How to read this

  • The length is the distance from source to device. The return trip is already counted.
  • Figures are for copper. Aluminium of the same size has about 1.6 times the resistance.
  • The "current it handles" is a cautious estimate. Real installations follow the local code table.
  • A wire running hot and a lamp dimming at the far end are two different problems. Pick a gauge that answers both.

Frequently asked questions

Q. Can AWG 14 carry 3 A?

Yes. This gauge is comfortable up to 14.8 A.

Q. How far can I run it?

The drop stays under 3% for 139.1 m at 230 V, 72.6 m at 120 V, or 7.3 m at 12 V.

Q. How many mm² is AWG 14?

2.081 mm², from a diameter of 1.628 mm. The nearest size in the other family is 2.5mm².

Q. How hot does the wire get?

Every metre turns 0.07 W into heat. Over ten metres that is a 0.7 W heater left running.