Wire gauge·AWG 2 · 100A
AWG 2
67.5m
100A · Europe 230 V

AWG 2 carrying 100 A — 1.02 V over 10 m

33.631 mm² of copper, 0.00051 Ω per metre. Carrying 100 A, a ten-metre run there and back loses 1.02 V.

You need thicker wire · Current it handles 90.4A

Diameter
6.544 mm
Cross-section
33.631 mm²
Resistance per metre
0.00051 Ω
Current it handles
90.4 A
Drop over 10 m
1.02 V
Heat per metre
5.11 W

Length within 3%

Lose the same 0.36 V and it is 3% of a 12 V system but 0.16% of a 230 V one. That is why car wiring looks so thick, and why a long 12 V light run dims at the far end. This page works out the length that stays under 3% for each voltage separately.

  • car 12 V3.5 m
  • truck 24 V7 m
  • North America 120 V35.2 m
  • Europe 230 V67.5 m

The match in the other family

The United States names wire by AWG number; most of the world names it by cross-section in mm². The two never line up exactly, so each page shows the nearest match by area. When substituting, err toward the thicker one.

16mm²16mm²

Nearby cells

Same gauge, other currents

Same current, other gauges

How to read this

  • The length is the distance from source to device. The return trip is already counted.
  • Figures are for copper. Aluminium of the same size has about 1.6 times the resistance.
  • The "current it handles" is a cautious estimate. Real installations follow the local code table.
  • A wire running hot and a lamp dimming at the far end are two different problems. Pick a gauge that answers both.

Frequently asked questions

Q. Can AWG 2 carry 100 A?

No. This gauge tops out around 90.4 A, so step up to something thicker.

Q. How far can I run it?

The drop stays under 3% for 67.5 m at 230 V, 35.2 m at 120 V, or 3.5 m at 12 V.

Q. How many mm² is AWG 2?

33.631 mm², from a diameter of 6.544 mm. The nearest size in the other family is 16mm².

Q. How hot does the wire get?

Every metre turns 5.11 W into heat. Over ten metres that is a 51.1 W heater left running.