Wire gauge·6mm² · 50A
6mm²
24.1m
50A · Europe 230 V

6mm² carrying 50 A — 2.87 V over 10 m

6 mm² of copper, 0.00287 Ω per metre. Carrying 50 A, a ten-metre run there and back loses 2.87 V.

You need thicker wire · Current it handles 29.5A

Diameter
2.764 mm
Cross-section
6 mm²
Resistance per metre
0.00287 Ω
Current it handles
29.5 A
Drop over 10 m
2.87 V
Heat per metre
7.17 W

Length within 3%

Lose the same 0.36 V and it is 3% of a 12 V system but 0.16% of a 230 V one. That is why car wiring looks so thick, and why a long 12 V light run dims at the far end. This page works out the length that stays under 3% for each voltage separately.

  • car 12 V1.3 m
  • truck 24 V2.5 m
  • North America 120 V12.6 m
  • Europe 230 V24.1 m

The match in the other family

The United States names wire by AWG number; most of the world names it by cross-section in mm². The two never line up exactly, so each page shows the nearest match by area. When substituting, err toward the thicker one.

AWG 105.261mm²

Nearby cells

Same gauge, other currents

Same current, other gauges

How to read this

  • The length is the distance from source to device. The return trip is already counted.
  • Figures are for copper. Aluminium of the same size has about 1.6 times the resistance.
  • The "current it handles" is a cautious estimate. Real installations follow the local code table.
  • A wire running hot and a lamp dimming at the far end are two different problems. Pick a gauge that answers both.

Frequently asked questions

Q. Can 6mm² carry 50 A?

No. This gauge tops out around 29.5 A, so step up to something thicker.

Q. How far can I run it?

The drop stays under 3% for 24.1 m at 230 V, 12.6 m at 120 V, or 1.3 m at 12 V.

Q. How many mm² is 6mm²?

6 mm², from a diameter of 2.764 mm. The nearest size in the other family is AWG 10.

Q. How hot does the wire get?

Every metre turns 7.17 W into heat. Over ten metres that is a 71.7 W heater left running.