phenolic foam · 120mm
R 6
U 0.162 W/m²·K
phenolic foam, 120 mm — R 6
120 mm divided by a conductivity of 0.02 gives an R-value of 6. The U-value is 0.162, so a square metre leaks 3.24 W across a 20-degree difference.
Standards it meets
- Korean central-region wall 0.17
- loose standard 0.30
- Material
- phenolic foam
- Thickness
- 120 mm
- Thermal conductivity
- 0.02 W/m·K
- Thermal resistance
- 6 m²·K/W
- U-value
- 0.162 W/m²·K
- Heat lost per square metre
- 3.24 W
- As concrete
- 9.6 m
Thickness for the same performance
This is the number that shows what insulation is worth. Matching 100 mm of XPS with concrete alone would take 5.7 metres of it. No one builds a wall like that — which is why a concrete building only gets warm once a thin layer of insulation is added.
- vacuum panel42 mm
- rigid polyurethane138 mm
- extruded polystyrene168 mm
- graphite EPS186 mm
- white EPS216 mm
- glass wool222 mm
- mineral wool240 mm
- cellulose252 mm
- timber780 mm
- plasterboard1080 mm
- concrete9600 mm
Nearby cells
Same material, other thicknesses
Same thickness, other materials
How to read this
- Thermal resistance is the thickness in metres divided by the conductivity. Bigger is better.
- The U-value adds 0.17 of surface resistance and then flips the total. Smaller is better.
- Resistances add across layers, so a whole wall is the sum of its parts.
- Conductivity varies by product; the values here are typical for the material.
Frequently asked questions
Q. What is the R-value of 120 mm of phenolic foam?
6 — 120 mm in metres divided by a conductivity of 0.02.
Q. And the U-value?
0.162. That is 6.17 — the resistance plus 0.17 of surface — turned upside down, and a square metre leaks 3.24 W across 20 degrees.
Q. How much concrete would match it?
9.6 metres.
Q. Which standards does it meet?
At 0.162 it clears 2 of them.